The AI industry continues to innovate rapidly, now moving into powerful agentic services requiring gigawatt data centers, megawatt racks, wafer-scale and panel-scale processors. The recently proposed 800 VDC data center rack power delivery network (PDN) infrastructure enables the swiftly escalating power demands of AI processors. While 800 VDC rack power distribution will yield reduced thermal losses versus 48 VDC rack power distribution within AI factories, a very significant power loss challenge remains along the lower-voltage processor point-of-load (PoL) final-stage PDN, primarily due to insufficiently low DC–DC converter current gain and current density capabilities.
Every basis point (0.01%) improvement in AI data center power usage effectiveness (PUE) has growing value. Just one basis point of PUE for a 1GW AI factory is equivalent to the installation of ten additional megawatt racks of compute capacity and significantly increased return on investment for AI data center operators.
AI processors consume about half of the total energy delivered to the data centers that host them, so minimizing the thermal power losses associated with energizing them is of primary concern. Energy savings in the rack-level compute and networking trays have a very significant positive impact on PUE. Specifying the most efficient power architecture for all power domain rails of chiplet-based panel-scale processors is essential to optimize top-level AI data center PUE. Panel-scale AI processors typically incorporate chiplet GPUs, HBMs, CPUs, LPDDR5 SDRAMs, and Ethernet switch network processors with co-packaged optics. Figure 1 illustrates a conceptual circa 2029 200mm by 230mm panel-scale processor.